Primary and Secondary Fuse Recommendations for all Three Phase Transformers
Primary General Purpose Transformers |
Secondary General Purpose Transformers |
||||||||
VA |
208 |
240 |
480 |
600 |
208 |
240 |
380 |
480 |
|
3K |
12 (20) |
9 (17.5) |
5 (9) |
4 (7) |
1.2 |
9 |
6 |
5 |
|
6K |
25 (40) |
20 (35) |
9 (15) |
8 (12) |
2.5 |
20 |
12 |
9 |
|
9K |
35 (60) |
30 (50) |
15 (25) |
12 (20) |
35 |
30 |
18 |
15 |
|
15K |
60 (100) |
50 (90) |
25 (45) |
20 (35) |
60 |
50 |
30 |
25 |
|
30K |
110 (200) |
100 (176) |
50 (90) |
40 (70) |
110 |
100 |
60 |
50 |
|
45K |
175 (300) |
150 (250) |
70 (125) |
60 (100) |
175 |
150 |
90 |
70 |
|
75K |
300 (500) |
250 (450) |
125 (225) |
100 (175) |
300 |
250 |
150 |
125 |
|
112.5K |
400 (750) |
350 (650) |
175 (300) |
150 (250) |
400 |
350 |
225 |
175 |
|
150K |
600 (1000) |
500 (900) |
250 (450) |
200 (350) |
600 |
500 |
390 |
250 |
|
225K |
- |
- |
350 (650) |
300 (500) |
800 |
700 |
450 |
350 |
|
300K |
- |
- |
500 (900) |
400 (700) |
1200 |
1000 |
600 |
500 |
|
500K |
- |
- |
800 (1500) |
650 (1200) |
1800 |
1600 |
1000 |
800 |
Primary Drive Isolation Transformers |
Secondary Drive Isolation Transformers |
|||||
VA |
230 |
460 |
575 |
230 |
460 |
|
7.5K |
25 (45) |
12 (20) |
10 (17.5) |
25 |
12 |
|
11K |
35 (60) |
17.5 (30) |
15 (25) |
35 |
17.5 |
|
14K |
45 (85) |
25 (40) |
20 (35) |
45 |
25 |
|
20K |
70 (125) |
35 (60) |
30 (50) |
70 |
35 |
|
27K |
85 (150) |
45 (80) |
35 (60) |
90 |
45 |
|
34K |
110 (200) |
60 (100) |
45 (80) |
110 |
60 |
|
40K |
150 (250) |
70 (1250 |
60 (100) |
150 |
70 |
|
51K |
175 (300) |
80 (150) |
70 (150) |
175 |
80 |
|
63K |
200 (350) |
100 (175) |
80 (150) |
200 |
100 |
|
75K |
250 (450) |
125 (225) |
100 (175) |
250 |
125 |
|
93K |
300 (500) |
150 (250) |
125 (225) |
300 |
150 |
|
118K |
400 (700) |
200 (350) |
150 (250) |
400 |
200 |
|
145K |
500 (800) |
250 (450) |
200 (350) |
500 |
250 |
|
175K |
- |
300 (500) |
225(400) |
600 |
300 |
|
220K |
- |
350 (650) |
300 (500) |
700 |
350 |
|
275K |
- |
450 (850) |
350 (600) |
900 |
450 |
|
330K |
- |
600 (1000) |
450 (800) |
1200 |
600 |
|
440K |
- |
700 (1350) |
600 (1000) |
1400 |
700 |
Fuse = 1*125% next size higher if primary current is 9 Amp or higher. No secondary fusing required.
(Fuse) = (1*125%) next size smaller if primary current is 9 Amp or higher. Secondary fusing is required. See chart for size.
OUTPUT FUSE = 1*125% next size higher if secondary current is 9 Amps or higher. Recommend fuse size per NEC450.3[B] and commercially available fuse types.